Bradford White heat pump water heater

Bradford White AeroTherm (RE2H…-1NCTT models) error codes

Covers: AeroTherm Series heat pump water heater, previous generation (RE2H50S*-1NCTT, RE2H65T*-1NCTT, RE2H80T*-1NCTT; sold as RE2H50S10/RE2H65T10/RE2H80T10 and Bradford White Connect versions RE2H50S10-CON/RE2H65T10-CON/RE2H80T10-CON)

Every code listed in Bradford White's own manual for this series, with what it means and what Bradford White says to do. Last checked 2026-10-03.

Is this your model? The I&O manual 238-52169-00C cover lists models RE2H50S*-1NCTT, RE2H65T*-1NCTT, RE2H80T*-1NCTT. Bradford White's documentation page lists this manual under both 'AeroTherm® Series Heat Pump' and 'AeroTherm® Series Heat Pump with Bradford White Connect™'. Spec sheets 1902 (RE2H50S10, RE2H65T10, RE2H80T10) and 1901 (with -CON Connect models) are on the same page. Control (manual page 5): 3-digit display with mode LEDs (Heat Pump (Only), Hybrid, Electric (Only), Vacation), MODE, UP/DOWN, ENTER and FILTER buttons, and a red filter light. Fault codes are letter-prefixed (F2-F24, FC-FL, 'bAd linE'). Connect units use an external Bradford White Connect adapter (manual 238-54090-00A).

CodeLabelWhat the manual says it means
FCControl checks to ensure evaporator is free of frost. Continuously verifies that T3a sensor (evaporator inlet temperature) is greater than 20°F after 30 minutes of run time.
FdControl checks to ensure evaporator superheat is OK (controlled by EEV). Continuously verifies the temperature difference between T3a sensor (evaporator inlet temperature) and T3b sensor (evaporator outlet temperature) is greater than 5°F after 30 minutes of run time. Control also verifies that T3a is greater than 10°F less than T5 ambient sensor.
FEControl checks to ensure the compressor discharge temperature never exceeds 240°F. Continuously verifies that T4 sensor (compressor outlet temperature) is less than 240°F every minute of run time.
FFControl checks to ensure the EEV is operating properly and valve rotation is within range.
FIControl checks to ensure evaporator superheat is <20°F AND the EEV position is <450 after 30 minutes of run time. If outside these limits, this provides an early indication of a refrigerant leak. (Note: Target superheat is generally 10°F, and EEV generally operates at a position much lower than 450). [On some models]
FJControl checks to ensure that the AC current draw is ≤ 20.5A while the compressor and lower heating element are both enabled. If current draw is > 20.5A, the compressor will be disabled.
FLControl checks to ensure that T3 and T3b evaporator inlet and outlet temperatures are within 2.5°F of the T5 ambient temperature 20 minutes after defrost begins.
F2T2 tank temperature sensor failure. Just before compressor starts, control checks T2 sensor is within 30°F - 170°F temperature range.
F3Compressor failure. Control energizes compressor, but current sensor detects no current flow.
F4Fan failure.
F5T3a sensor (evaporator inlet temperature) failure. The control detects the thermistor output is at or nearly shorted or open circuit.
F6T3b sensor (evaporator outlet temperature) failure. The control detects the thermistor output is at or nearly shorted or open circuit.
F7T4 sensor (compressor outlet) failure. The control detects the thermistor output is at or nearly shorted or open circuit.
F8T5 sensor (ambient temperature) failure. The control detects the thermistor output is at or nearly shorted or open circuit.
F9Lower heating element failure. Control energizes lower element, but current sensor detects no current flow.
F10Upper heating element failure. Control energizes upper element, but current sensor detects no current flow.
F11Dry tank fault. This test is run within the first 22 minutes after the water heater has powered on (the compressor is engaged for 20 minutes after a 2 minute wait for the high and low side pressures to equalize). The tank temperature, T2, is read and verified it has not risen more than 5°F. If it has, this indicates there is not enough water in the tank for water heater operation. After 1 failed dry tank test, "F11" is displayed. After 5 failed tests, an audible alarm will sound.
bAd linE (F12)The voltage is too low at power-up. The control monitors the input line voltage one minute after power-up, and if the voltage is below 155 VAC, the fault code will be displayed.
F13Stuck key fault. This indicates there is a button on the front panel that is stuck down. This button is inoperable. Other buttons work normally. If the button becomes free, the fault code will clear by itself.
Dirty Filter (F14)Filter LED is on, and audible alarm is sounding. Filter is too dirty to enable proper function of water heater. Number of "Dirty Filter" counts are stored in the "F14" code and can be monitored via the control when it is placed in Diagnostics Mode. The evaporator is operating at a colder temperature than the ambient temperature as measured by T5.
F15DataFlash fault. The microcontroller has detected a problem in the DataFlash (permanent memory storage).
F16Anode Depleted. Anode LED is on, and the audible alarm is sounding. The control has calculated that the anode rod has been mostly consumed, or the time in operation has exceeded the replacement timeline threshold. [On some models]
F17Anode Depletion miswire condition or shorted to ground. The control has detected that the anode circuit has a corrosion current signal ≤0.25mA. [On some models]
F18Current transformer miswired. F3, F9, and F10 fault codes have all occurred during the same heating cycle.
F19Low line voltage.
F20Condensate drain port blocked. Water heater will only operate in standard/electric mode until the drain port is cleared and the sensor is no longer in contact with water.
F21Application Update Failure. A problem occurred while updating the control application.
F22Parametric Data Update Failure. A problem occurred while updating parametric data.
F23Micro A/D Failure. The control has detected a microcontroller input port has failed.
F24T1 tank temperature sensor failure. Just before compressor starts, control checks T1 sensor is within 30°F - 170°F temperature range.

Bradford White's manual for this series does not list error codes; see the troubleshooting section below.

Safety first

From the manufacturer's manual for this series.

Troubleshooting without a code

Owner maintenance

Sources