Bradford White Heat pump RE2H (-1NCWT models) error code FI

What it means

Control checks to ensure evaporator superheat is <20°F AND the EEV position is <450 after 30 minutes of run time. If outside these limits, this provides an early indication of a refrigerant leak. (Note: Target superheat is generally 10°F, and EEV generally operates at a position much lower than 450.)

The manual says the control must detect this 10 time(s) before the code is displayed.

Source: Bradford White Heat Pump Water Heater RE2H50, RE2H65, RE2H80 mini manual / quick reference (service), 238-52395-00 (file rev A), page 3

What Bradford White says to do

These steps involve electrical testing or parts replacement. Bradford White's manuals tell owners to leave that work to a qualified service technician.

Probable refrigerant leak. Find and Repair. Check T3a, T3b, T5 sensor mounting, wiring and resistance. Check EEV wiring at control, coil placement, and operation.

Last checked 2026-10-03.